SUP2H-PV series surge protector | SUP2H1-PV | SUP2H1-PV | SUP2-PV | |
UCPV(VDC) | 1000V | 1200V | 1500V | |
Max system discharge current (8/20μs)Imax | 40KA | 40KA | 40KA | |
Voltage Protection level(up) | ≤4.0KV | ≤4.5KV | ≤4.5KV | |
Voltage Protection level at 5kA(up) | ≤3.6KV | ≤4.0KV | ≤5.0KV | |
Integrated Fuse breaking capacity/interrupting rating | 40KA/1000vdc | 40KA/1200vdc | 40KA/1500vdc | |
technology | Short-Circuit interruption (SCI)overcurrent protection | |||
Operating temperature range(TU) | -40℃ to +80℃ | |||
Nominal discharge current (8/20 μs){(DC+/DC-)>PE}(In) | 20KA | |||
Response time (A) | <25ns | |||
Operating State/Fault indication | Green (good)/RED(repiace) | |||
Conductor rating and cross-sectional Area | Minimum | 60/75℃ 1.5mm2/14AWG solid/flexible | ||
Maximum | 60/75℃ 35mm2/2AWG stranded/25mm2/4AWG flexible | |||
Mounting | 35mm DIN rall per EN 60715 | |||
Enclosure material | UL 90VO thermopiastic | |||
Degree of Protection | IP20 | |||
Capacity | 3 Modules,DIN 43880 | |||
Standards information | IEC 61643-31 Type2,IEC 61643-1 ClassⅡ | |||
product Warranty | Five Years |
Remote Contact signaling Type | Changeover contact |
AC switching capacity(volts/Amps) | 250V/0.1A |
DC switching capacity(volts/Amps) | 250V/0.1A;125V/0.2A;75V/0.5A |
Conductor ratings and cross-sectional area for remote Contact signal terminals |
60/75℃Max,1.5mm2/14AWG solid/flexible |
Ordering | Order from Catalog numbers Above |
Does not apply to 1200Vdc
1.Use a suitable electrical insulator to keep a 10mm min.safety distance from the PV-SPD and other grounfed parts in the housing.
2.No metal covers are in the area of the module release as shown.
Conductor and busbars for use in photovoltaic systems
IEC 60364-7-712(DIN VDE 0100 part 712)